Omega CDTX-90 Manuel d'utilisateur Page 5

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 20
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 4
page 3
CDTX-90-1 System Power/Loop Connections
Stand-alone application, no current loop used
Transmitter
4
3
2
1
Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +
Power Supply
DC 12 - 24 V
Power
Supply
Power
Supply
Connection to a PLC with built-in power supply
PLC
Power Supply
Ground
Power
Supply
Loop Input
4-20 mA
Loop Input
4-20 mA
Internal PLC
Connection
Connection to a PLC/Recorder, separate supply
PLC or Recorder
Loop Input
4-20 mA in
Loop Input
4-20 mA in
DC 12 - 24 V
Power
Supply
Power
Supply
Example: Two transmitters connected to PLC/Recorder
with separate power supply
Transmitter 2
4
3
2
1
DC 12 - 24 V
Power
Supply
Power
Supply
Transmitter 1
4
3
2
1
Transmitter
4
3
2
1
Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +
Transmitter
4
3
2
1
Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +
Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +
Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +
PLC or Recorder
Channel 1
4-20 mA in
Channel 1
4-20 mA in
Channel 2
4-20 mA in
Channel 2
4-20 mA in
Terminals
Terminals
Terminals
Terminals
-
+
-
+
-
+
-
+
-
+
-
+
-
+
AUX power required for all CDTX-90 systems.
CDTX-90-1 Terminal connections
Terminals 5-6: Open-collector Output
A transistor output, programmable (see CALIBRATE menu) as High or Low setpoint with
adjustable hysteresis and proportional pulse (to 400 pulses per minute maximum).
May be disabled (Off) if not used.
Terminals 3 and 4: Loop Power
12-24 VDC ±10% system power
and current loop output.
Max. loop impedance:
50 Ω max. @ 12 V
325 Ω max. @ 18 V
600 Ω max. @ 24 V
Internal open-collector
output circuit
Output --
Output +
Isolation
15W
S
D
Terminals 1-2: Auxiliary power
Provides DC power to measurement
circuit. Required for all CDTX-90
systems.
Terminals 7-10: Sensor input
7 is conductivity input
8 is temperature input
9 is the isolated signal ground
10 is the sensor earth ground